A Modified Lyapunov-Function Based Control Scheme for Two-Leg Three-Level T-Type Grid-Tied Inverter with LCL Filter

Loading...
Thumbnail Image

Date

Journal Title

Journal ISSN

Volume Title

Publisher

IEEE

Access Rights

info:eu-repo/semantics/closedAccess

Abstract

In this study, a modified Lyapunov-function based control scheme is proposed for two-leg three-phase three-level T-type grid-tied inverter with LCL filter. Proposed inverter topology has only two legs and thus it provides 1/3 reduction on the total switch count. The conventional Lyapunov-function based control is modified by adding an additional capacitor voltage feedback (CVFB) loop. This additional feedback provides better suppression of LCL filter resonance and improves the dynamic response of the system. The performance of modified Lyapunov-function based control scheme and operation of the proposed inverter are validated with MATLAB/Simulink environment. Simulation results show that the proposed inverter together with the control scheme can generate balanced three-phase voltages and currents with only two legs. Furthermore, capacitor feedback loop significantly improves the transient response of the system.

Description

4th International Conference on Power Electronics and their Applications (ICPEA) -- SEP 25-27, 2019 -- Elazig, TURKEY

Keywords

T-type inverter, reduced number of switches, two-leg inverter, three-level inverter, Lyapunov-function based control

Journal or Series

2019 4Th International Conference on Power Electronics and Their Applications (Icpea)