Globally stable control of three-phase three-wire shunt active power filters

dc.contributor.authorKomurcugil, Hasan
dc.contributor.authorKukrer, Osman
dc.date.accessioned2026-02-06T18:34:04Z
dc.date.issued2007
dc.departmentDoğu Akdeniz Üniversitesi
dc.description.abstractThis paper proposes a new control strategy for three-phase three-wire shunt active power filters. The idea in this strategy is to form an energy-like Lyapunov function in terms of the active filter states and then determine the control law that makes the time derivative of the Lyapunov function always negative for all values of the states. It is shown analytically that a globally stable control is possible. The references for the active filter currents are obtained by subtracting the measured load currents from the generated source current references. The amplitude of the source currents is adjusted by employing a proportional-integral regulator in the voltage control loop. Matlab simulations are performed for a nonlinear load drawing quasi-square-wave currents from the mains. Simulation results show that the Lyapunov function-based control strategy not only eliminates the load current harmonics successfully, but also exhibits excellent transient response during large load variations.
dc.identifier.doi10.1007/s00202-006-0012-8
dc.identifier.endpage418
dc.identifier.issn0948-7921
dc.identifier.issue5
dc.identifier.orcid0000-0003-4728-6416
dc.identifier.scopus2-s2.0-34248155769
dc.identifier.scopusqualityQ1
dc.identifier.startpage411
dc.identifier.urihttps://doi.org/10.1007/s00202-006-0012-8
dc.identifier.urihttps://hdl.handle.net/11129/11625
dc.identifier.volume89
dc.identifier.wosWOS:000246202900008
dc.identifier.wosqualityQ3
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherSpringer
dc.relation.ispartofElectrical Engineering
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260204
dc.subjectactive power filter
dc.subjectLyapunov's direct method
dc.subjectharmonic compensation
dc.titleGlobally stable control of three-phase three-wire shunt active power filters
dc.typeArticle